Author:JeffFell–ApplicationEng. Date:April3,2019
External
http://www.abb.us/drives
Industry–Industrial
Document#:LVD‐EOTN109U‐EN
Revision:C
ProductCategories:RETA‐01,FENA‐xx
Error Code 16#0127 = Connection Request Error: Invalid output size.
Reason: The connection words size is too large to fit in the programmed word array size in the
PLC.
Things to check:
□ Check the programmed connection size in the PLC and the drive (example the drive is
sending 13 words and the PLC is programmed to 10 words).
□ Also check to make sure the Comm Format is programmed to Data – INT in the PLC.
Error Code 16#0005 = Connection Request Error: Bad Class.
Reason: There is a mismatch in the selected profile between the PLC and Drive.
Things to check:
□ Check the Profile setting in the drive (FENA-xx parameter 51.02 or RETA-01 51.16) for
the selected Assembly Instances that were chosen in the PLC.
□ There is a mismatch in the selected profile (example the drive is programmed for ODVA
Profile and the PLC is programmed for ABB Profile).
□ Also check the programmed connection size in the PLC and the drive (example the drive
is sending 2 words and the PLC is programmed to 6 words).
□ Also check to make sure the Comm Format is programmed to Data – INT in the PLC.
Error Code 16#0109 = Connection Request Error: Invalid connection size (Invalid Input size).
Reason: The connection words size for the Input is too large to fit in the programmed word
array size in the PLC.
Things to check:
□ Check the programmed connection size in the PLC and the drive (example the drive is
sending 2 words and the PLC is programmed to 4 words).
□ Also check to make sure the Comm Format is programmed to Data – INT in the PLC.
Error Code 16#0111 = Requested Packet Interval (RPI) out of range.
Reason: The programmed RPI rate is lower then allowed by the Fieldbus option.
Things to check:
□ Increase the RPI rate in RSLogix 5000, this can be found under the Connection Tab.